RunTru A4AH4E36A1C30A Submittal 3.0 Ton Convertible Air Handler Instruction Manual

Home » RunTru » RunTru A4AH4E36A1C30A Submittal 3.0 Ton Convertible Air Handler Instruction Manual

RunTru - Logo

Submittal
3.0 Ton
Convertible Air Handler
A4AH4E36A1C30A

RunTru A4AH4E36A1C30A Submittal 3 0 Ton Convertible Air Handler - Cover

September 2022
A4AH4E36A1C-SUB-1A-EN

Outline Drawing

RunTru A4AH4E36A1C30A Submittal 3 0 Ton Convertible Air Handler - Outline Drawing 1 RunTru A4AH4E36A1C30A Submittal 3 0 Ton Convertible Air Handler - Outline Drawing 2 RunTru A4AH4E36A1C30A Submittal 3 0 Ton Convertible Air Handler - Outline Drawing 3

 

M I N I M UM U N I T CL EA R A NCE TABLE
SER V I CE CLEA R A NCE
(R ECOM M E N DED )
SIDES 2″
FRONT 2 I”
BACK 0″
INLET DUCT I”
OUTLET DUCT N / A

NOTE: THIS UNIT IS APPROVED FOR INSTALLATION CLEARANCES TO COMBUSTIBLE MATERIAL AS STATED ON THE UNIT RATING NAMEPLATE

ALL DIMENSIONS ARE REFERENCE DIMENSIONS

RunTru A4AH4E36A1C30A Submittal 3 0 Ton Convertible Air Handler - Outline Drawing 4

PRODU CT DIMENSIONS
Air Handler Model A B c D E F H Flow Control Gas Line Braze
A4AH4E36A 1C30A 51.27 23.50 21.50 21.75 7.01 9.66 24.59 TXV 7/8
All dimensions are in inches

Product Specifications

MODEL A4AH4E36A1C30A
RATED VOLTS/PH/HZ 208-230/ 1/60
RATINGS(a) See O.D. Specifications
INDOOR COIL -Type Plate Fin
Rows – F.P.I. 4 – 14
Face Area (sq. ft.) 4.59
Tube Size (in.) 3/8
Refrigerant Control TXV
Drain Conn. Size (in.) (b) 3/4 NPT
DUCT CONNECTIONS See Outline Drawing
INDOOR FAN – Type Centrifugal
Diameter-Width ( n.) 11X 8
No. Used 1
Drive – No. Speeds Direct – 5 Ccl
CFM vs. in. w.g. See Fan Performance Table
No. Motors – H.P. 1- 1/2
Motor Speed R.P.M. 1050
Volts/ Ph/Hz 208-230/ 1/60
F.L. Amps 4.1
FILTER
Filter Furnished? (b) No
REFRIG ERANT R-410A
Ref. Line Connections Brazed
Coupling or Conn. Size – in. Gas 7/8
Coupling or Conn. Size – in. Liq. 3/8
DIM ENSIONS H x W x D
Crated ( n.) 52-3/4 x 27-1/2 x 25-1/2
Uncrated 51-3/8 x 23-1/2 x 21-1/8
WEIGHT
Shipping (Lbs.)I Net (Lbs.) 155/ 144

(a) These Air Handlers are A.H.R.I certified with various Split System Air Conditioners and Heat Pumps (AHRI STANDARD 210/240). Refer to the Split System Outdoor Unit Product Data Guides for performance data.
(b) 3/4″ Male Plastic Pipe (Ref: ASTM 1785­76)
(c) ECM Motor
(d) Remote filter required.

Minimum Airflow CFM

A4AH4E36A1C30A
Heater                                                                                      Minimum Heat Speed Tap
With Heat Pump Without Heat Pump
BAYHTR1504BRK, BAYHTR1504LUG,
BAYHTR1505BRK, BAYHTR1505LUG
Low Low
BAYHTR1508BRK, BAYHTR1508LUG,
BAYHTR1510BRK, BAYHTR1510LUG
Med-High Med-Low
BAYHTR1523BRK Med-High Med
BAYHTR1517BRK,BAYHTR3517LUG,
BAYHTR3510LUG
High Med

Heater Pressure Drop Table

Airflow
CFM
Number of Racks Heater Racks
1 2 3 4 Heater Model No. of Racks
Air Pressure Drop -Inches W.G. BAYHTR 1504 1
1800 0.02 0.04 0.06 0.14 BAYHTR 1505 1
1700 0.02 0.04 0.06 0.14 BAYHTR 1508 2
1600 0.02 0.04 0.06 0.13 BAYHTR 1510 2
1500 0.02 0.04 0.06 0.12 BAYHTR 1517 3
1400 0.02 0.04 0.06 0.12 6AYHTR3510 3
1300 0.02 0.04 0.05 0.11 BAYHTR3517 3
1200 0.01 0.04 0.05 0.10 BAYHTR3515 3
1100 0.01 0.03 0.05 0.09 BAYHTR 1523 4
1000 0.01 0.03 0.04 0.09 BAYHTR 1525 4
900 0.01 0.03 0.04 0.08
800 0.01 0.03
700 0.01 0.02
600 0.01 0.02

Performance and Electrical Data

  1. See Product Data or Air Handler nameplate for approved combinations of Air Handlers and Heaters.
  2. Heater model numbers may have additional suffix digits.

Table 1. Air Flow Performance

A4AH4E36A1C30A
EXTERNAL STATIC
(in w.g)
A RFLOW
Speed Taps: 208 – 230 VOLTS
High Med-High Med t Med-Low Low
0.1 1492 1418 1302 1268 1140
0.2 1460 1385 1266 1230 1096
0.3 1426 1349 1228 1190 1050
0.4 1390 1311 1187 1147 1002
0.5 1352 1271 1144 1101 952
0.6 1311 1229 1099 1053 899
0.7 1269 1184 1051 1003 845
1. Values are with wet coil, no filter, and no heaters
2. CFM Correction for dry coil = Add 3%
3. † = Factory Setting
4. In downflow applications, airflow must not exceed 1600 cfm due to condensate blowoff.
5. Low = Tap 1,Med-Low = Tap 2, Med = Tap 3, Med-High= Tap 4, High = Tap 5

Table 2. Electrical Data

A4AH4E36A1C30A
Heater Model No. No. of Circuits/ Phases 240 Volt 208 V
Capacity Heater Amps per Circuit Minimum Circuit Ampacity Maximum Overload Protection Capacity Heater Amps per Circuit Minimum Circuit Ampacity Maximum Overload Protection
kW BTUH kW BTUH
No Heater 4.1* 5 lS 4.1* s 15
BAYHTR1S04BRK BAYHTR1S04LUG 1/ 1 3.8 13100 16.0 25 25 2.9 9800 13.8 22 2S
BAYHTRlSOSBRK BAYHTRlSOSLUG 1/ 1 4.8 16400 20.0 30 30 3.6 12300 17.3 27 30
BAYHTR1S08BRK BAYHTR1S08LUG 1/ 1 7.7 26200 32.0 45 4 5.8 19700 27.7 40 40
BAYHTRlS OBRK BAYHTRlS OLUG 1/ 1 9.6 32800 40.0 55 60 7.2 24600 34.6 48 50
BAYHTR1S17BRK-
Circuit 1(a)
2/ 1 9.6 32800 40.0 55 60 7.2 24600 34.6 48 50
BAYHTR1S 7BRK-
Circuit 2
4.8 16400 20.0 25 25 3.6 12300 17.3 22 25
BAYHTR1S23BRK-
Circuit 1(a)
2/ 1 9.6 32800 40.0 55 60 7.2 24600 34.6 48 50
BAYHTR1S23BRK-
Circuit 2
9.6 32800 40.0 50 50 7.2 24600 34.6 43 45
BAYHTR3S 10LUG 1/3 9.6 32800 23. 1 33 35 7.2 24600 20.0 30 30
BAYHTR3S 17LUG 1/3 14.4 49100 34.6 48 so 10.8 36900 30.0 42 45
BAYHTR1S17BRK
with single circuit power source kit BAYSPEKT201A
1/ 1 14.4 49100 60.0 83 90 10.8 36900 51.9 73 80
* = Motor Amps

(a) MCA and MOP for circuit 1 contains the motor amps.

Features and Benefits

  • Galvanized metal cabinet with captured foil face insulation
  • 2% or less air leakage
  • R-4.2 Insulating Value
  • Multi-Position UP/Down Flow, Horizontal Left /Right
  • ALL Aluminum Coil
  • Electric Heaters with polarized plug connections (sold as accessory)
  • R-410A Thermal Expansion Valve
  • ECM Motor (3..0 – 5 Ton Models)
  • Low Voltage Pigtail Connections
  • Draw Through Design
  • Horizontal Drain pan
  • Single Color
  • Fused 24V Power
  • 5 year warranty
  • Optional extended warranty availabel

Important: Condensate management kit is required for all 5 ton air handler models installed in downflow applications.

About Trane and American Standard Heating and Air Conditioning
Trane and American Standard create comfortable, energy efficient indoor environments for residential applications. For more information, please visit www.trane.com or www.americanstandardair.com.

The manufacturer has a policy of continuous data improvement and it reserves the right to change design and specifications without notice. We are committed to using environmentally conscious print practices.

A4AH4E36A1C-SUB-1A-EN 06 Sep 2022