MAYTAG MG2R Gas Furnace Instruction Manual

Home » Maytag » MAYTAG MG2R Gas Furnace Instruction Manual

MAYTAG MG2R Gas Furnace


For 80+ and 90+ Single Stage Furnaces

Refer to the Installation Instructions provided with the furnace for the proper heating and cooling speeds for your application.

Red LED Flash Error/Condition
Flash codes stored in memory (auto-erased after 14 days)
1 System Lockout (Retries Exceeded)
2 Pressure Switch Stuck Closed
3 Pressure Switch Stuck Open
4 Open High Temperature Limit Switch
5 Flame Sensed>4.25 Seconds with Gas Valve De-Energized
6 Open Flame RO Switch
8 Ignitor Relay Error
10 Open Fuse
11 Ignitor Open
12 Inducer Relay Error
Flash codes NOT stored in memory
7 Low Flame Sense Signal
9 Twinning Fault
Off Control Failure / No Power / Internal Fault / IRQ Loss
Gas Heating Lockout (Gas valve energized when it should be de-energized)
Or Gas valve De-energized when it should be Energized
Rapid Flash Reverse Polarity
Continuous On Normal Operation

If any of the original wire as supplied with the furnace must be replaced, it must be replaced with wiring material having a temperature of at least 105 C.

Use copper conductors only.

Cool Motor SPEED DIPSWITCH SETTING (S1-1, S1-2, S1-3)
1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3
Position OFF OFF OFF ON OFF OFF ON ON OFF OFF ON OFF OFF OFF ON OFF ON ON ON OFF ON ON ON ON
Motor SPEED Cool Y T1 T2 T3 T4 T1+T2 T1 T1 T1
Heat Motor SPEED DIPSWITCH SETTING (S2-1, S2-2)
1 2 1 2 1 2 1 2
Position OFF OFF ON OFF ON ON OFF  ON
Motor SPEED Heat W T1 T2 T3 T4
Fan Motor SPEED DIPSWITCH SETTING (S2-3, S2-4)
1 2 1 2 1 2 1 2
Position OFF OFF ON OFF OFF  ON ON ON
Motor SPEED Fan G T1 T2 T4 T1+T2

WIRING DIAGRAM