LUTRON CP-3000 Flexible 3000 Amp Current Probe
Product Information
Product Name: Flexible 3000 Amp Current Probe
Model: CP-3000
Manufacturer: LUTRON ELECTRONIC
Certifications: ISO-9001, CE, IEC1010
Features
- Range: 30 A/ 300 A/ 3000 A
- Output Sensitivity: 100 mV/ A, 10 mV/ A, 1 mV/ A
- Output Voltage: 3 ACV (30 A, 300 A, 3000 A)
- Flexible Probe Length: 600 mm (23.6 inches)
- Optional current probe for DW: 6093, DW-6095
- * When change the new probe, the calibration procedures are not necessary to be executed.
- * Signal output use the banana plugs, durable and safety.
- * Power supply is from the meter (DW-6093, DW-6095 ), battery is not necessary.
Battery power, AC to DC adapter power
30 A/300 A/3000 A, 100 mV/A, 10 mV/A, 1 mV/A
For 3 phase power analyzer DW-6093, DW-6095
Specifications
- Measurement Ranges: 30 A/ 300 A/ 3000 A 3 ranges, switch selectable
- 1st range value : 30 A
- 2nd range value : 300 A
- 3rd range value : 3000 A
- Output sensitivity: 100 mV/A, 10 mV/A, 1 mV/A, AC coupled.
- Frequency Range: 45 to 400 Hz
- Accuracy tested under 50/60 Hz.
- Accuracy: ± 1% of range value Linear to 100% of range value
- Accuracy is specified that the measured conductor’s position is on the center of ” Flexible current probe “.
- 50/60 Hz..
- 23 ± 5 ℃
- Phase error: < ± 1.5°
- 50/60 Hz..
- Conductor position sensitivity: ± 2 % of range value.
- Recommend the measured conductor position should > 25 mm ( 1″ ) away from the ” Probe locker “.
- Linearity: ± 0.2 % of reading value from 10 %to 100% of range value.
- External field influence: increase ± 1.5 % of range value max..
- Recommend the distance between different ” Flexibel current probe ” should > 200 mm ( 8″ ).
- Minimum load: 100 K ohm for specified accuracy.
- Enclosure material: UL 94-V0 rated.
- Safety: IEC 1010, Categories III 600V.
- Power Supply: Power supply is from the meter (DW-6093, DW-6095 ), battery is not necessary.
- Power supply voltage from DW-6093, DW-6095 is DC 8V± 1V
- Operating Temperature: 0 to 50℃℃ ( 32 t℉o 122 ).℉
- Operating Humidity: Less than 80% RH.
- Dimension:
- Main circuit unit :
105 x 56.5 x 33 mm.
( 4.1 x 2.2 x 1.3 inch ). - Flexible probe :
600 mm x 14.5 mm DIA.
23.6 inch x 0.57 inch DIA. - Cable length :
3.4 meters ( 11.2 feet ). - DC plug size :
5.5 mm x 2.5 mm DIA.
- Main circuit unit :
- Weight: 480 g ( 1.06 LB ).
- Accessory Included: Operating manual …………………1 PC.
- Enclosure Material: UL 94-V0 rated
Product Usage Instructions
- Ensure the power supply is connected to the meter (DW-6093, DW-6095). The probe does not require a separate battery.
- Connect the signal output plug (+, red) and signal output plug (-, black) to the appropriate ports on the device or instrument you are using.
- Set the desired measurement range using the 3000A/ 300A/ 30A range switch on the main circuit unit.
- Position the flexible probe around the conductor you wish to measure. It is recommended to keep a distance of at least 25 mm (1 inch) between the measured conductor and the probe locker.
- Ensure there is a distance of at least 200 mm (8 inches) between different flexible current probes to avoid external field influence.
- Make sure the measured conductor’s position is on the center of the flexible current probe for accurate measurements.
- Verify that the power LED lamp on the main circuit unit is illuminated, indicating that the device is powered on.
- Read the measurement values from the device or instrument you are using, taking into account the output sensitivity and voltage specifications mentioned in the product information.
FRONT PANEL DESCRIPTIONS
- 3-1 Flexible current probe
- 3-2 Probe locker
- 3-3 Main circuit unit
- 3-4 3000A/300A/30A range switch
- 3-5 Cable
- 3-6 DCV power plug
- 3-7 Signal output plug ( +, red )
- 3-8 Signal output plug ( -, black )
- 3-9 Power LED lamp