Literature E7EU High Airflow Blower Kit for Cooling Airflow Instruction Manual

Home » Literature » Literature E7EU High Airflow Blower Kit for Cooling Airflow Instruction Manual

Literature E7EU High Airflow Blower Kit for Cooling Airflow

Product Information

The High Airflow Blower Kit is designed to increase the airflow of the factory installed E7 blower assembly. This kit enhances the cooling airflow of the unit.

Important Safety Information

Before servicing the equipment, it is crucial to read all
instructions provided in the manual. Pay attention to safety warnings and special notes highlighted in the manual. Safety markings are used throughout the manual to indicate the seriousness of potential hazards, which should not be ignored. Failure to follow safety warnings and improper servicing could result in personal injury, death, or property damage.

Dip Switch Settings and Airflow Data

The table below shows the dip switch settings and corresponding airflow data:

Dip Switch Setting External Static Pressure (in W.C.) Airflow (CFM)
1/4 0.1 1278
2/5 0.2 1359
3/7 0.3 1318
4/8 0.4 – 0.7 Varying values
0.8 0.8 1287
0.9 0.9 1250
1.0 1.0 1213

Notes

  1. Airflow values were measured with a 23kW heater kit and clean factory air filter installed, without a cooling coil cabinet attached.
  2. If using a 15kW or 17kW electric heat, add 50 CFM to the airflow values. If using a 10kW or 12kW electric heat, add 100 CFM to the airflow values.
  3. The pressure drop of a clean factory air filter is 0.08 inch W.C.

E7 Furnace with High Airflow Blower Kit Electrical Data

The table below provides the electrical data for the E7 furnace with the High Airflow Blower Kit:

Model Number Circuit A MCA Circuit A MOP Circuit B MCA Circuit B MOP Single Supply MCA Single Supply MOP
E7E*-010H 59 60 59 60
E7E*-012H 37 40 30 30 67 70
E7E*-015H 56 60 26 30 85 90
E7E*-017H 59 60 35 35 91 100
E7E*-020H 59 60 52 60 111 125
E7E*-023H 59 60 60 60 119 125

Note: Always refer to this table to ensure the correct circuit breaker is used.

Product Usage Instructions

  1. Disconnect all power to the unit and remove the door. Remove the left access panel and disconnect the motor power and signal wires from the control board.
  2. Remove the 4 screws securing the blower housing and slide the assembly out of the unit.
  3. Install the new assembly in the same location, ensuring that the housing flanges slide underneath the blower deck tabs.
  4. Route the motor power and signal wires to the board and connect them according to the existing wiring diagram.
  5. Adjust the HEAT and COOL dip switch settings for the desired airflow.
  6. Reinstall the access panel and door, and restore power to the unit.

Important: Before starting the installation process, please read all instructions carefully and follow the safety warnings provided in the manual to ensure proper installation and avoid any potential hazards.

Required: Replace Electrical Data Labels

As part of the installation process, apply the electrical data labels provided in this High Airflow Blower Kit on top of the E7 electric furnace’s original rating labels. This step is necessary to ensure accurate electrical data information for the unit.

INSTALLATION INSTRUCTIONS

  • HIGH AIRFLOW BLOWER KIT FOR COOLING AIRFLOW
  • This kit is intended to provide increased airflow over the factory installed E7 blower assembly.

IMPORTANT SAFETY INFORMATION

INSTALLER: Please read all instructions before servicing this equipment. Pay attention to all safety warnings and any other special notes highlighted in the manual. Safety markings are used frequently throughout this manual to designate a degree or level of seriousness and should not be ignored. WARNING – Indicates a potentially hazardous situation that if not avoided, could result in personal injury or death.

  1. Disconnect all power to the unit and remove the door.
  2. Remove the left access panel, and disconnect the motor power and signal wires from the control board.
  3. Remove the 4 screws securing the blower housing and slide the assembly out of the unit.
  4. Install the new assembly in the same location while making sure the housing flanges slide underneath the blower deck tabs.
  5. Route the motor power and signal wires to the board and connect them according to the existing wiring diagram.
  6. Adjust the HEAT and COOL dipswitch settings for the desired airflow.
  7. Reinstall access panel and door and restore power to the unit.

WARNING

ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury or property damage. Improper servicing could result in dangerous operation, serious injury, death or property damage.

  • Before servicing, disconnect all electrical power to furnace.
  • When servicing controls, label all wires prior to disconnecting. Reconnect wires correctly.
  • Verify proper operation after servicing.
DIP SWITCH SETTING EXTERNAL STATIC PRESSURE (IN W.C.)
1/4 2/5 3/7 4/8 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
0 0 0 0
1 0 0 0
0 1 0 0
1 1 0 0
0 0 1 0
1 0 1 0 1203
0 1 1 0 1308 1265 1225
1 1 1 0 1399 1359 1318 1278 1237
0 0 0 1 1485 1440 1405 1362 1318 1278 1241
1 0 0 1 1544 1507 1470 1434 1397 1360 1323 1287 1250 1213
0 1 0 1 1639 1606 1566 1526 1491 1453 1420 1381 1338 1296
1 1 0 1 1696 1659 1623 1586 1549 1512 1476 1439 1402 1365
0 0 1 1 1756 1714 1680 1647 1613 1575 1540 1499 1460 1420
1 0 1 1 1802 1767 1731 1695 1660 1624 1588 1553 1517 1481
0 1 1 1 1850 1817 1782 1751 1715 1676 1641 1606 1569 1524
1 1 1 1 1898 1865 1829 1795 1760 1724 1690 1657 1622 1584

NOTES

  1. Airflow values were measured with 23kW heater kit and clean factory air filter installed, and no cooling coil cabinet attached.
  2. If using 15kW or 17 kW of electric heat, add 50 cfm to these values. If using 10kW or 12kW, add 100 cfm to these values.
  3. Pressure drop of clean factory air filter is 0.08 inch W.C.

Table 1. Dipswitch Settings and Airflow Data

Model Number: E7E*- Circuit A Circuit B Single Supply
MCA MOP MCA MOP MCA MOP
010H 59 60 59 60
012H 37 40 30 30 67 70
015H 59 60 26 30 85 90
017H 56 60 35 35 91 100
020H 59 60 52 60 111 125
023H 59 60 60 60 119 125

Note: Always reference this table to make sure you use the correct circuit breaker.

Table 2. E7 Furnace with High Airflow Blower Kit Electrical Data

REQUIRED: REPLACE ELECTRICAL DATA LABELS

This High Airflow Blower Kit contains electrical data labels that are to be applied on top of the E7 electric furnace’s original rating labels as part of installation of this kit.
Please follow these instructions:

  1. Locate the English and French electrical data labels included within the High Airflow Blower Kit. Also locate the English and French electrical data labels that are on the E7 electric furnace.
  2. Carefully apply the English and French electrical data labels from the High Airflow Blower Kit ON TOP of the original English and French electrical data labels on the E7 electric furnace, as shown in Figure 1.
  3. On the electrical data labels, CIRCLE the model of the E7 electric furnace into which the High Airflow Blower Kit was installed to correctly identify which row of electrical data is correct for that particular unit.
  • Specifications & illustrations subject to change without notice or incurring obligations (10/22). O’Fallon, MO, © Nortek Global HVAC LLC 2022. All Rights Reserved.

1044063A (Replaces 10440630)