EPH CONTROLS CDT2-24 Room Thermostat Hardwired Instruction Manual

Home » EPH CONTROLS » EPH CONTROLS CDT2-24 Room Thermostat Hardwired Instruction Manual

EPH-Controls-logo

EPH CONTROLS CDT2-24 Room Thermostat Hardwired

EPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-PRODUCT

Product Information

The CDT2-24 Room Thermostat is a hardwired thermostat used for controlling room temperature. It has various features and settings that can be customized to meet your needs. The thermostat has factory default settings which can be adjusted according to your preferences. It also has a frost protection feature to prevent freezing temperatures. The thermostat has a keypad lock function to prevent unauthorized access and a high and low temperature limitation feature. The switching differential can be adjusted to control the temperature accurately. The thermostat has a blue backlight that activates for 10 seconds after any button is pressed.

Specifications

  • Power supply
  • Power consumption
  • Temperature control range
  • Ambient temperature
  • Contact rating
  • Dimensions
  • Temperature sensor
  • Switching differential
  • Frost protection

Product Usage Instructions

Mounting:

  1. The thermostat should be mounted on a wall in the room where the heating is to be controlled.
  2. The mounting height should be 1.5 meters above the floor level.
  3. Choose a location that allows the sensor to measure the room temperature accurately.
  4. Avoid mounting the thermostat in direct sunlight or near other heating/cooling sources.
  5. The thermostat can be mounted on recessed conduit boxes, surface mounting boxes, or directly on walls.

Installation

  1. Before starting any work on the electrical connections, ensure that the thermostat is disconnected from the mains power.
  2. Only qualified electricians or authorized service staff should open the thermostat.
  3. Refer to the wiring diagram and wire the thermostat accordingly.
  4. Tighten the fastening screw to secure the thermostat.

Frost Protection
The thermostat has an in-built frost protection feature. The details of how this feature operates are not provided in the manual extract.

Button/Symbol Description

  • Room temperature On/Standby button
  • Set button
  • Heating ON symbol
  • Reset button
  • Set point increase button
  • Set point decrease button

Resetting the Thermostat

  1. To reset the thermostat, press and hold the Set button for 5 seconds. The screen will display “dEL”.
  2. Press the RESET button on the side of the thermostat.

Keypad Lock and Unlock

  • To lock the keypad, press and hold the “+” and “-” buttons for 5 seconds. The screen will display a lock symbol indicating that the keypad is locked.
  • To unlock the keypad, press and hold the “+” and “-” buttons for 5 seconds. The lock symbol will disappear from the screen, indicating that the keypad is unlocked.

Operating Instructions

CAUTION!
Before commencing any work on the electrical connections, you must first disconnect the thermostat from the mains. None of the 24V connections must be live until the installation has been completed and the housing is closed. Only qualified electricians or authorised service staff are permitted to open the thermostat. There are parts that may carry mains voltage behind the cover. The thermostat must not be left unsupervised when open. (Prevent non specialists and especially children from gaining access to it.)
Important: Keep this documentEPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-2

Prior to setting the thermostat, it is neccessary to complete all required settings described in this section.

Factory default settingsEPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-1

  • Contacts: Volt Free
  • Temperature indicator: °C
  • Switching dierential: 0.4°C
  • In built frost protection: 5°C
  • High and Low temp. limitation: OFF
  • Blue backlight activated : for 10 secs after any button is pressed
  • Keypad lock: OFF

Specifcations & wiring

  • Power supply: 24Vac 50Hz
  • Power consumption: 8 VA
  • Temp. control range: 5 … 35°C
  • Ambient temperature: 0 … 50°C
  • Contact rating: 7A 24Vac
  • Dimensions: 84 x 84 x 30mm
  • Temperature sensor: NTC 10K Ohm @ 25°C
  • Switching differential: Adjustable from 0.2/0.4/0.6/0.8/1.0°C
  • Frost protection: Only operational in stand by modeEPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-4

Mounting

The mounting height should be 1.5 meters above the oor level. The thermostat should be wall mounted in the room where the heating is to be controlled. The place of installation should be chosen so that the sensor can measure the room temperature as accurately as possible. Choose the mounting location to prevent direct exposure to sunlight or other heating / cooling sources when mounted.
The unit can be fitted to:

  1. Recessed conduit boxes
  2.  Surface mounting boxes
  3. Directly on walls

Installation

  • Slacken the fastening screw on the bottom of the thermostat with a Philips head screwdriver.
  • The thermostat is hinged and can be opened 180 degrees.
  • Mount the unit as described in section 3.
  • Wire the thermostat according to the wiring diagram.
  • Close the thermostat and tighten the fastening screw.

Wiring diagramEPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-3

If 24Vac output is required, terminals L & 2 must be electrically linked.

Frost protectionEPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-15°C

  • Frost protection is built into this thermostat, it is pre xed at 5°C and is not adjustable.
  • It will only be activated when the thermostat is in the stand by mode and the room temperature reaches 5°C.

Button / Symbol descriptionEPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-5

Resetting the thermostat

  • It is necessary to reset the thermostat prior to initial use.
  • Press and hold the EPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-6button for 5 seconds. dEL will appear on the screen.
  • Press the EPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-7 button on the side of the thermostat.

Keypad lock and unlock EPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-1off

  • To lock the keypad, press and hold the EPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-8andEPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-9 buttons for 5 seconds. EPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-1-will appear on the screen. The keypad is now locked.
  • To unlock the keypad, press and hold theEPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-8 and EPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-9buttons for 5 seconds. mEPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-1-will disappear from the screen. The keypad is now unlocked.

High and Low temperature limitationEPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-1off

  • An upper and lower temperature limit may be chosen.
  • Press and hold theEPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-13 andEPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-6 buttons for 10 seconds. “Limit OFF” will appear on the screen.
  • Press the EPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-8button to select “Limit ON” mode.
  • Press the EPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-6button to confrm you wish to adjust the high limit temperature.
  • Press theEPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-8 andEPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-9 buttons to select the high limit temperature.
  • Press theEPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-6 button to select the low limit temperature mode.
  • Press theEPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-8 andEPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-9 buttons to select the low limit temperature.
  • Press theEPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-6 button and the thermostat is ready for operation. “Limit” will appear on the screen.
  • To deactivate High and Low temperature limitation.
  • Press and hold theEPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-13 and EPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-6buttons for 10 seconds. “Limit ON” will appear on the screen.
  • Press the EPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-9button to deactivate this function. “Limit OFF” will appear on the screen.
  • Press the EPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-6button and the thermostat is ready for operation.

Adjusting the switching differential

  • Press theEPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-6 button once, Diff set will appear on the screen.
  • The factory default switching differential of 0.4C will appear on the screen.
  • Press the EPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-9andEPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-8 buttons to select the desired differential from 0.2 – 1°C.
  • Press theEPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-6 button to return to normal operation.

Adjusting the setpoint temperature

  • Press the EPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-8or EPH-CONTROLS-CDT2-2- Room-Thermostat-Hardwired-fig-9buttons to adjust the temperature setpoint.

EPH Controls Ireland
[email protected] www.ephcontrols.com