Contents
EBTRON GTM116e Thermal Dispersion Airflow And Temperature Measurement
BACnet Protocol Implementation Conformance Statement
| Date: 2/14/2024 | Vendor Name: Ebtron, Inc. |
| Product Name: Gold Series GTM116e | Application Software Version: 4.17 |
| Product Model Number: GTM116e | Firmware Revision: 8.28 |
| Product Description: Airflow and Temperature Measurement Device with Integral Relative Humidity | BACnet Protocol Revision: 22
. |
BACnet Standardized Device Profile (Annex L):
- BACnet Operator Workstation (B-OWS)
- BACnet Building Controller (B-BC)
- BACnet Advanced Application Controller (B-AAC)
- BACnet Application Specific Controller (B-ASC)
- BACnet Smart Sensor (B-SS)
- BACnet Smart Actuator (B-SA)
BACnet Interoperability Building Blocks Supported (Annex K):
| DS-RP-B | DS-RPM-B |
| DS-WP-B | DS-WPM-B |
| DS-COV-B | DM-DDB-B |
| DM-DOB-B | DS-DCC-B |
| DM-RD-B | NM-FDR-A |
Segmentation Capability
- Segmented requests supported
- Window Size
- Segmented responses supported
- Window Size
Standard Object Types Supported
Data Link Layer Options
- BACnet IP, (Annex J)
- Option: Register as a Foreign Device
- ISO 8802-3, Ethernet (Clause 7)
- ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)
- ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s)
- MS/TP master (Clause 9), baud rate(s):
- MS/TP slave (Clause 9), baud rate(s):
- Point-To-Point, EIA 232 (Clause 10), baud rate(s):
- Point-To-Point, modem, (Clause 10), baud rate(s):
- LonTalk, (Clause 11), medium:
- Other:
Device Address Binding:
Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain other devices.)
- Yes
- No
Networking Options
- Router, Clause 6 – List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc.
- Annex H, BACnet Tunneling Router over IP
- BACnet/IP Broadcast Management Device (BBMD) Does the BBMD support registrations by Foreign Devices?
- Yes
- No
Character Sets Supported:
Indicating support for multiple character sets does not imply that they can all be supported simultaneously.
- ANSI X3.4/UTF-8
- ISO 10646 (UCS-2)
- IBM/Microsoft DBCS
- ISO 10646 (UCS-4)
- ISO 8859-1
- JIS C 6226
If this product is a communication gateway, describe the types of non-BACnet equipment/networks(s) that the gateway supports:
| TABLE 2 – Standard Object Types Supported (GTM116e) | |||||||
| Object | Create Object
Service |
Delete Object
Service |
Optional
Properties Supported |
Writeable Properties | Proprietary Properties | Property Range Restrictions | Special Requirements |
| Device – GTM116e | No | No | • Description
• Location • Active COV Subscriptions |
• Object Identifier
• Object Name • Description • Location • APDU Timeout |
• BBMD Remote Address
• BBMD Remote Port • Time To Live • Service Tag |
None | |
| Analog Input 1 –
AMD Airflow |
No | No | • Description
• Reliability • COV Increment |
• Units
• Out of Service • COV Increment • Present Value |
None | Units: FPM, CFM, MPS, LPS | |
| Analog Input 2 –
AMD Temperature |
No | No | • Description
• Reliability • COV Increment |
• Units
• Out of Service • COV Increment • Present Value |
None | Units: °C or °F | |
| Analog Input 3 –
AMD Pressure |
No | No | • Description
• Reliability • COV Increment |
• Units
• Out of Service • COV Increment • Present Value |
None | Units: iWG or Pa | -B |
| Analog Input 4 –
AMD Alarm Status |
No | No | • Description
• Reliability • COV Increment |
• Out of Service
• Present Value |
None | None | |
| Analog Input 21 –
RH |
No | No | • Description
• Reliability • COV Increment |
• Out of Service
• COV Increment • Present Value |
None | -P w/H | |
| Analog Input 22 –
Dew Point |
No | No | • Description
• Reliability • COV Increment |
• Units
• Out of Service • COV Increment • Present Value |
None | Units: °C or °F | -P w/H |
| Analog Input 23 –
Enthalpy |
No | No | • Description
• Reliability • COV Increment |
• Units
• Out of Service • COV Increment • Present Value |
None | Units: Btu/lb or kJ/kg | -P w/H |
| Analog Value 1 –
AMD Area |
No | No | • Description
• Reliability |
None | Units: sq ft or sq m | ||
| Analog Value 10 –
Traverse Status |
No | No | • Description
• Reliability |
Present Value | None | Only write 0 – 3 | |
| Analog Value 21 –
Node 1 Velocity |
No | No | • Description
• Reliability |
None | Units: FPM, MPS | Enabled in AV 10 | |
| Object | Create Object Service | Delete Object Service | Optional Properties Supported | Writeable Properties | Proprietary Properties | Property Range Restrictions | Special Requirements |
| Analog Value 22 –
Node 2 Velocity |
No | No | • Description
• Reliability |
None | Units: FPM, MPS | Enabled in AV 10 | |
| Analog Value 23 –
Node 3 Velocity |
No | No | • Description
• Reliability |
None | Units: FPM, MPS | Enabled in AV 10 | |
| Analog Value 24 –
Node 4 Velocity |
No | No | • Description
• Reliability |
None | Units: FPM, MPS | Enabled in AV 10 | |
| Analog Value 25 –
Node 5 Velocity |
No | No | • Description
• Reliability |
None | Units: FPM, MPS | Enabled in AV 10 | |
| Analog Value 26 –
Node 6 Velocity |
No | No | • Description
• Reliability |
None | Units: FPM, MPS | Enabled in AV 10 | |
| Analog Value 27 –
Node 7 Velocity |
No | No | • Description
• Reliability |
None | Units: FPM, MPS | Enabled in AV 10 | |
| Analog Value 28 –
Node 8 Velocity |
No | No | • Description
• Reliability |
None | Units: FPM, MPS | Enabled in AV 10 | |
| Analog Value 29 –
Node 9 Velocity |
No | No | • Description
• Reliability |
None | Units: FPM, MPS | Enabled in AV 10 | |
| Analog Value 30 –
Node 10 Velocity |
No | No | • Description
• Reliability |
None | Units: FPM, MPS | Enabled in AV 10 | |
| Analog Value 31 –
Node 11 Velocity |
No | No | • Description
• Reliability |
None | Units: FPM, MPS | Enabled in AV 10 | |
| Analog Value 32 –
Node 12 Velocity |
No | No | • Description
• Reliability |
None | Units: FPM, MPS | Enabled in AV 10 | |
| Analog Value 33 –
Node 13 Velocity |
No | No | • Description
• Reliability |
None | Units: FPM, MPS | Enabled in AV 10 | |
| Analog Value 34 –
Node 14 Velocity |
No | No | • Description
• Reliability |
None | Units: FPM, MPS | Enabled in AV 10 | |
| Analog Value 35 –
Node 15 Velocity |
No | No | • Description
• Reliability |
None | Units: FPM, MPS | Enabled in AV 10 | |
| Analog Value 36 –
Node 16 Velocity |
No | No | • Description
• Reliability |
None | Units: FPM, MPS | Enabled in AV 10 | |
| Analog Value 41 –
Node 1 Temperature |
No | No | • Description
• Reliability |
None | Units: °C or °F | Enabled in AV 10 | |
| Analog Value 42 –
Node 2 Temperature |
No | No | • Description
• Reliability |
None | Units: °C or °F | Enabled in AV 10 | |
| Analog Value 43 –
Node 3 Temperature |
No | No | • Description
• Reliability |
None | Units: °C or °F | Enabled in AV 10 | |
| Analog Value 44 –
Node 4 Temperature |
No | No | • Description
• Reliability |
None | Units: °C or °F | Enabled in AV 10 | |
| Analog Value 45 –
Node 5 Temperature |
No | No | • Description
• Reliability |
None | Units: °C or °F | Enabled in AV 10 | |
| Analog Value 46 –
Node 6 Temperature |
No | No | • Description
• Reliability |
None | Units: °C or °F | Enabled in AV 10 | |
| Analog Value 47 –
Node 7 Temperature |
No | No | • Description
• Reliability |
None | Units: °C or °F | Enabled in AV 10 |
| Object | Create Object Service | Delete Object Service | Optional Properties
Supported |
Writeable Properties | Proprietary Properties | Property Range Restrictions | Special Requirements |
| Analog Value 48 –
Node 8 Temperature |
No | No | • Description
• Reliability |
None | Units: °C or °F | Enabled in AV 10 | |
| Analog Value 49 –
Node 9 Temperature |
No | No | • Description
• Reliability |
None | Units: °C or °F | Enabled in AV 10 | |
| Analog Value 50 –
Node 10 Temperature |
No | No | • Description
• Reliability |
None | Units: °C or °F | Enabled in AV 10 | |
| Analog Value 51 –
Node 11 Temperature |
No | No | • Description
• Reliability |
None | Units: °C or °F | Enabled in AV 10 | |
| Analog Value 52 –
Node 12 Temperature |
No | No | • Description
• Reliability |
None | Units: °C or °F | Enabled in AV 10 | |
| Analog Value 53 –
Node 13 Temperature |
No | No | • Description
• Reliability |
None | Units: °C or °F | Enabled in AV 10 | |
| Analog Value 54 –
Node 14 Temperature |
No | No | • Description
• Reliability |
None | Units: °C or °F | Enabled in AV 10 | |
| Analog Value 55 –
Node 15 Temperature |
No | No | • Description
• Reliability |
None | Units: °C or °F | Enabled in AV 10 | |
| Analog Value 56 –
Node 16 Temperature |
No | No | • Description
• Reliability |
None | Units: °C or °F | Enabled in AV 10 | |
| Network Port 1 | No | No | • Description
• Network Number • Network Number Quality • Mac Address • APDU Length • BACnet IP Mode • IP Address • IP UDP Port • IP Subnet Mask • IP Default Gateway • IP DNS Server • IP DHCP Enable • Foreign Device BBMD Address • Foreign Device Subscription Lifetime |
• BACnet IP Mode
• Foreign Device BBMD Address • Foreign Device Subscription Lifetime |
None | None | None |
- EBTRON Inc. 1663 Hwy. 701 S., Loris SC 29569
- Toll Free: 800.2EBTRON (800.232.8766)
- Fax: 843.756.1838
- Internet: www.EBTRON.com
Specifications
- Product Name: Gold Series GTM116e
- Product Model Number: GTM116e
- Product Description: Airflow and Temperature Measurement Device with Integral Relative Humidity
- Vendor Name: Ebtron, Inc.
- Application Software Version: 4.17
- Firmware Revision: 8.28
- BACnet Protocol Revision: 22
Frequently Asked Questions (FAQ)
Q: Does the BBMD support registrations by Foreign Devices?
A: Yes, the BBMD supports registrations by Foreign Devices.
Q: Is static device binding supported for two-way communication?
A: Yes, static device binding is supported for two-way communication with MS/TP slaves and certain other devices.