DAUDIN iO-GRID C PLC PROFINET Coupler Instruction Manual

Home » DAUDIN » DAUDIN iO-GRID C PLC PROFINET Coupler Instruction Manual

DAUDIN-LOGO

DAUDIN iO-GRID C PLC PROFINET Coupler

DAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-PRODUCT

Product Information

Product Name
2301EN V1.0.0 & SIEMENS PLC PROFINET Connection Operating Manual

Table of Contents

  1. Example Remote I/O Module System Configuration List
  2. Coupler Parameter Settings
  3. Siemens S7-1200 Connection Setup

1. Example Remote I/O Module System Configuration List

Part No. Specification Remarks
GF2-C004T PROFINET Coupler
GF2-DI01T 16-channel digital input module, Sink, 24VDC
GF2-DQ01T 16-channel digital output module, Sink, 24VDC
GF2-AI01T 4-channel analog input module (-10… 10VDC,
0…10VDC0…5VDC)
GF2-AQ01T 4-channel analog output module (-10… 10VDC,
0…10VDC0…5VDC)
GFPS-0202 Power 24V / 48W

Product Description

  • The coupler connects to the communication port (PROFINET) on Siemens S7-120.
  • The coupler is in charge of the management and dynamic configuration of I/O parameters and so on.
  • The power module is standard for remote I/Os and users can choose the model or brand of power module they prefer.

 Coupler Parameter Settings

This chapter explains how a coupler connects to Siemens S7-1200, detailed introduction on, please refer to the i-Designer User Manual.

 Preceding Operation of Software Setup

  1. Connect with the coupler module using a Micro-USB cable.
  2. Plug your Micro-USB cable to the Micro-USB port on your coupler module.
  3. Make sure the fieldbus is powered and then open the i-Designer setup program.

Coupler Module Parameters Setup

Coupler module connection illustrationDAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-FIG-2

Before setting up the coupler module, please confirm that the I/O modules are lined up closely on the Fieldbus

 Coupler Software Setup

  1. Make sure that the module is powered and connected to the USB port.DAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-FIG-4
  2. Click to launch the software.DAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-FIG-5
  3. Select C Series Module Configuration.DAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-FIG-6
  4. Click on the Setting Module icon.DAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-FIG-7
  5. Enter the Setting Module page for the C-series.DAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-FIG-8
  6. Click on Connect.DAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-FIG-9
  7. Please Stop the System warning appears.DAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-FIG-10
  8. Click on System Stop.DAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-FIG-11
  9. Select the coupler module and click on Auto Addressing.DAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-FIG-12
  10. Once addressing is completed, modules will appear on the Module List on the left.DAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-FIG-13
  11. Click on the coupler module to open the Setting Module pageDAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-FIG-14
  12. Type in the device name and if the transmission should continue once the connection is interrupted (Timelock at 0).DAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-FIG-16
  13. Type in your IP address (default IP address:192.168.1.20).DAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-FIG-15

Siemens S7-1200 Connection Setup

This chapter explains how to use the TIA Portal program to connect S7-1200 and a coupler and add a remote I/O module. For detailed information, please refer to the “SIMATIC STEP 7” section in the user manual

Siemens S7-1200 hardware connectionDAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-FIG-17
Siemens S7-1200 IP Address and Connection Setup
  1. Open the TIA Portal, click on “Device Configuration” and then the “PROFINET Port” menuDAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-FIG-18
  2. Click on “Ethernet Address” and type in the IP address (same as the coupler at 192.168.1.XXX)
  3. GSDML Document Installation
    • Click on “Options” on the menu bar
    • Select “Manage GSD File” from the drop-down menu
    • Choose the GSDML file you want and click on “Install”DAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-FIG-15DAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-FIG-21DAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-FIG-22
  4. Click on the “Topology View”
    • Select “PROFINET IO” on the right-side menu
    • Select “I/O” and choose to add “Dinkle I/O” to the PLC networkDAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-FIG-24
  5. Select “Network View”
    • Right-click on the I/O port and select “Assign to a new I/O controller”DAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-FIG-25DAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-FIG-26
  6. Double-click on the icon of GF2-C004T DAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-FIG-26
  7. Select the IP address to connect to (the module’s default IP address is 192.168.1.20)DAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-FIG-28DAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-FIG-29
  8. VIII. Under the 【Equipment View】&【Hardware Menu】
    • Add modules in the same sequence as UI’s addressing
    • ※Attention! The sequence must be the same as UI’s addressing. Otherwise, the device cannot communicate normally.DAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-FIG-30DAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-FIG-31
  9. Click on “Network View”
    • Assign device namesDAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-FIG-32DAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-FIG-33
  10. Right-click on the device, select “Compile” and download it to PLC
    • Hardware (completely rebuilt)
    • Software (fully rebuilt)
    • Download to equipment (hardware configuration)
    • Download to equipment (download all of the software)DAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-FIG-34
  11. Register addresses are assigned based on the modules added EX: %I168.0 at the first DI, %I168.1 at the second DI, %IW2 at the first channel of AI, and %IW4 at the second channel of AIC DAUDIN-iO-GRID-C-PLC-PROFINET-Coupler-FIG-35