Algodue UEM63-4D R70 Single Phase Electricity Meter User Manual

Home » algodue » Algodue UEM63-4D R70 Single Phase Electricity Meter User Manual

Algodue UEM63-4D R70 Single Phase Electricity Meter User Manual

 63A THREE PHASE ENERGY METER

The communication protocols and the relevant softwares are available at www.algodue.com
WARNING! Device installation, wiring configuration and terminal cover sealing must be carried out only by qualified professional staff. Switch off the voltage before device installation.

AVAILABLE PACKAGES

Name Model COM port Nominal voltage, frequency Available wiring Tariff input S0

output

(Un, f) 3.4.3
UEM63-4D R70 RS485 MODBUS RS485 3×230/400…3×240/415 V,

50/60 Hz

The following preset packages are available:
MID: MID certified meter, with reset function only on partial counters.
MID S*: MID certified meter, with reset function only on partial counters, without reactive energy counters on display.
NONE: Meter without MID certification, with reset function only on partial counters.
RESET: Meter without MID certification, with RESET function on ALL counters.
*For MID S package, the device name changes: the S letter is added (e.g. UEM63-4DS R70).

OVERVIEW

Refer to picture B:

  1. Neutral terminal
  2. Backlight LCD display
  3. SET key
  4. UP key
  5. ENTER key
  6. Metrological LED
  7. Current and voltage terminals
  8. Safety-sealing (DO NOT REMOVE)

SYMBOLS ON FRONT PANEL (EXAMPLE)

Refer to picture D:
A. Device name
B. Serial number
C. Data Matrix
D. Protection class
E. Meter constant (metrological LED)
F. Base current (max current)
G. Working temperature
H. Accuracy class
I. Nominal voltage/frequency
J. Wiring type: =3phases 4wires 3currents
K. MID approval symbols
L. Type approval certification
If the device is NO MID version, “Cl.1 EN 62053-21” will be shown instead of H, K and L fields.

 TARIFF INPUT

The RS485 port allows to manage the device by MODBUS RTU/ASCII protocol. For device network connection, install a terminal resistance (RT=120…150 Ω) on the RS485 converter side and another one on the last device connected on the line. The maximum recommended distance for a connection is 1200m at 9600 bps. For longer distances, lower communication speed (bps), low-attenuation cables or signal repeaters are needed. Refer to picture E.
Default values: MODBUS RTU (8N1), 19200 bps

WIRING DIAGRAM

It is suggested to install a low power switch or some fuses on the voltage inputs for protection and in order to operate on the instrument without deactivating the plant.
Refer to picture F: 3.4.3 = 3 phases, 4 wires, 3 currents

Before instrument power ON, check if all connections are made in a proper way. Make sure that the voltage and current terminals are connected correctly. Moreover, make sure that low voltage ports, such as communication ports and/or SO ports, are connected to low voltage lines. These safety precautions may reduce the risk to damage the instrument in case of improper connections.

SYMBOLS ON DISPLAY

Refer to picture G:

  1.   Phase sequence:  = correct (123),  = wrong (132),
  2. System value
  3. Value phase number
  4. Different meanings according to the shown item:
    SEtUP: Setup page; InFO: Info page = not defined (e.g. one or more phases are missin
  5. Metrological parameters corrupted (Code: XX). Useless counter, to be returned to the Manufacturer
  6. S0 output active status
  7. Communication active status
  8. Setup page
  9. Main area
  10. Measuring unit area
  11. Partial counter Flashing=stopped counter
  12. 1 or 2 tariff counter value
  13. Balance counter value
  14. Inductive value
  15. Capacitive value
  16. Imported (>), exported (<) energy or power value

MEASUREMENTS

  SYMBOL MEASURE UNIT DISPLAY PORT
 INSTANTANEOUS VALUES                                                                                                                                              

V∑, V1, V2, V3

 

           V           

 

 

                 

 

       l

Voltage                                                                       
Line voltage                                                                   V12, V23, V31                          V                   l
Current                                                                         I∑, I1, I2, I3, IN            A             

                 

       n
Power factor                                                                  PF∑, PF1, PF2, PF3             –                   l
Apparent power                                                               S∑, S1, S2, S3           kVA                   n        n
Active power                                                                   P∑, P1, P2, P3           kW                    n        n
Reactive power                                                               Q∑, Q1, Q2, Q3          kvar                   n

 

       n
Frequency                                                                      f           Hz                  l
Phase sequence                                                             CW / CCW                         –                      l             l
 Power direction l l
 RECORDED DATA                                                                                                                                                              
Total active energy                                                          ∑, L1, L2, L3          kWh                   n        n
Total ind. and cap. reactive energy                                      ∑, L1, L2, L3         kvarh                    nv        n
Total ind. and cap. apparent energy                                    ∑, L1, L2, L3                   kVAh                   n             n
Tariff 1-2 energy counters                                                  T1 T2 ∑, L1, L2, L3 kWh, kvarh, kVAh           nv        n
Resettable partial energy counters PAR  kWh, kvarh, kVAh nv n
 Energy balance BAL  kWh, kvarh, kVAh nv n
 OTHER INFORMATION                                                         SYMBOL                       STATUS          DISPLAY     

 

 

 

                 

PORT
Present tariff                                                                   T1, T2             –                   l
Undervoltage/overvoltage                                                   AL             –                   l
Undercurrent/overcurrent                                                   AL             –                   l
Frequency out of range                                                    AL                                    –                   l
Partial counter status PAR / PAR Started / Stopped l l
S0 output status   Active l  

All the system counters (kWh∑, kvarh∑, kVAh∑) can be associated to S0 output.