6000VA – 10000VA

The ability to install up to four units in parallel means that the maximum redundancy level is always guaranteed

Ablerex-6000VA-10000VA-MARS-III-Tower-FIG-1

FEATURES

  • Maximum power availability: kVA=kW.
  • Up to 4 units in parallel, 3 + 1 redundancy possible with parallel kit.
  • Low running costs: the high efficiency VFI and ECO features minimise energy consumption.
  • User-friendly monitoring software can be downloaded free and is compatible with the main operating systems, for: monitoring functions, diagnostics, controlled shutdown of loads in the event of faults.
  • Cold start.
  • Wide input voltage and frequency ranges reduce battery switching, thereby increasing battery life and efficiency.
  • Flexible battery configuration to suit your uptime requirements.
  • Accurate calculated remaining uptime is shown on the display.
  • Hot-swappable batteries: the batteries can be replaced while the UPS is running.
  • Firmware can be upgraded easily to implement new features.
  • EPO and On/Off, with remote option.
  • 6-step operation test that can be activated manually.
  • RS232 and USB ports, slots for optional communication cards.

KEY OPTIONS

  • Cards: RS485, SNMP/web and relay card with dry contacts to send the UPS status to various systems, such as BMS, PLC, SCADA and AS400
  • Parallel kit.
  • External battery cabinets.
  • External manual bypass with additional sockets.

BACK PANEL

Ablerex-6000VA-10000VA-MARS-III-Tower-FIG-2

MARS III TOWER TECHNICAL DATA SHEET

MODEL MS III 6000 MS III 10000
 

POWER

VA 6000 10000
W 6000 10000
 

 

INPUT

Rated voltage* 110–280 Vac
Frequency 45–70 Hz
Power factor >0.99
 

 

 

 

 

 

OUTPUT

Rated voltage 200/208/220/230/240 Vac selectable
Voltage distortion <2% with linear load, <7% with distorting load
Voltage stability ±1%
Frequency 50/60 Hz (selectable)
Frequency stability £ 0.2% (free running)
Power factor 1
Crest factor 3:1
Waveform Pure sine wave
Output connection Terminal blocks
 

EFFICIENCY

VFI mode Up to 94%
ECO mode Up to 98%
 

 

 

 

 

 

GENERAL

Dimensions (WxDxH) mm 240x700x513 288x700x513
Weight (kg) 53 78
Alarms Audible and visual alarm alerts for: power failure, low battery, bypass transfer, and UPS fault.
Protection Overload, overheating, short circuit, deep discharge, battery overcharging.
Operating mode Multi-mode: VFl, ECO, frequency converter (CVCF)
Cold start from the battery without mains power  

Included

Parallel connection Up to 4 units for 3+1 redundancy
 

 

 

BATTERY

Battery type 12V VRLA, AGM (maintenance-free lead)
Uptime with internal battery (in minutes). 50% load 12 11
100% load 4 4
Charging time (90%) 4–6 hours
Battery expansion module dimensions (WxDxH) ** 288x663x661
 

 

ENVIRONMENTAL PARAMETERS

Operating temperature*** 0–40°C
Relative humidity 0%–90% (non-condensing)
Altitude (a.s.l.) <1000 m with no power derating, >1000 m with 1% derating for every 100 m.
Audible noise at 1 m. £60 dBA
 

 

 

CONNECTIVITY

Built-in communication ports USB, RS232, EPO On/Off contact, and additional slots for optional cards
User interface LCD and function keys (parameters: voltage, frequency, load percentage, battery voltage, output voltage, estimated uptime, UPS temperature).
Optional accessories Cards: SNMP, RS485 ModBus, dry relay contacts
Compatible software platforms Microsoft Windows, Linux, Mac OS, VMware
 

REGULATIONS

Standards IEC EN 62040-1, IEC EN 62040-2, IEC EN 62040-3
Marking CE