Contents
HH Series Evaporator Coils
Product Information
Specifications
- Nomenclature: H H57 1 24 A 185 A 21 02 AP
- Slab Number: Metering Device 1 = Piston (R-410A) 9 = Non Bleed HP-A/C TXV (R-410A)
- Nominal MBTUH: Cabinet Depth [1] A = 10
- Cabinet Opening Width [2]: 185 = 18 5/8, 225 = 22 5/8, 265 = 26 5/8, 305 = 30 5/8, 365 = 36 5/8, 425 = 42 5/8
- R-410A Pistons MBTUH Size: 12 = 41, 18 = 49, 24 = 53, 30 = 59, 36 = 67, 42 = 73, 48 = 76, 60 = 93
- AP: TXV Access Port [3] Product Code: 02 = Cased H
- Cabinet Opening Height: 21 = 21 1/4, A = Bi-directional airflow [1]
Dimensions
- Slab Number: H57, Nominal Tonnage: 1.5 – 3
- Slab Number: H58, Nominal Tonnage: 2 – 4
- Slab Number: H59, Nominal Tonnage: 2.5 – 4
- Slab Number: H60, Nominal Tonnage: 3 – 5
- Slab Number: H61, Nominal Tonnage: 3.5 – 5
- Slab Number: H62, H66, Nominal Tonnage: 3 – 5
Weight / Pallet Qty
- Slab Number: H57, Weight (lbs): 36, Pallet Quantity: 6
- Slab Number: H58, Weight (lbs): 41, Pallet Quantity: 4
- Slab Number: H59, Weight (lbs): 44, Pallet Quantity: 4
- Slab Number: H60, Weight (lbs): 50, Pallet Quantity: 4
- Slab Number: H61, Weight (lbs): 57, Pallet Quantity: 3
- Slab Number: H62, Weight (lbs): 61, Pallet Quantity: 3
- Slab Number: H66, Weight (lbs): 75, Pallet Quantity: 3
Airflow Data
Slab Number | 600 CFM | 800 CFM | 1000 CFM | 1200 CFM | 1400 CFM | 1600 CFM | 2000 CFM | 2400 CFM |
---|---|---|---|---|---|---|---|---|
H57 | 0.17 | 0.19 | 0.22 | 0.25 | – | – | – | – |
H58 | – | – | – | – | 0.05 | – | – | – |
H59 | – | – | – | – | – | – | – | – |
H60 | – | 0.18 | 0.20 | 0.22 | 0.24 | 0.26 | – | – |
H61 | – | – | 0.08 | 0.11 | 0.15 | 0.19 | 0.23 | – |
H62 | – | – | – | – | – | – | – | – |
H66 | – | – | – | – | – | – | – | – |
Product Usage Instructions
Step 1: Installation
Follow these steps to install the product
- Choose the appropriate cabinet opening width based on the dimensions provided.
- Ensure the cabinet depth is set to 10, as it is the only selectable option.
- Connect the metering device according to the desired configuration (Piston or Non Bleed HP-A/C TXV).
- Ensure the supply and return openings are sized correctly based on the formula provided.
- Place the product in the desired location and secure it properly.
Step 2: Operation
To operate the product, follow these steps
- Turn on the power supply.
- Set the desired temperature or mode using the control panel.
- Monitor the airflow and adjust the settings if necessary.
- Maintain regular maintenance and cleaning to ensure optimal performance.
Step 3: Troubleshooting
If you encounter any issues with the product, refer to the troubleshooting section in the user manual or contact customer support for assistance.
FAQ
- Q: What are the available cabinet opening widths?
- A: The available cabinet opening widths are 185 = 18 5/8, 225 = 22 5/8, 265 = 26 5/8, 305 = 30 5/8, 365 = 36 5/8, and 425 = 42 5/8.
- Q: How do I determine the correct supply and return opening sizes?
- A: The supply and return opening sizes can be calculated using the provided formula: (A – 1.50) x (B – 4 3/8), where A is the cabinet opening height and B is the cabinet opening width.
- Q: What is the warranty period for this product?
- A: Please refer to the warranty information provided in the user manual or contact customer support for details on the warranty period.
HH Series – Features & Nomenclature
Product Features
- High efficiency lanced fin design.
- “No-hassle” 5-year warranty. 10 year Limited Warranty available.
- R-22, R-410A, AC & Heat Pump compatible.
- All coils have durable packaging with bar coded labels on the box.
- Threaded expansion valves available factory installed or as a field installed kit.
- Coils are air pressure tested at 500 psi, leak tested with helium, sealed with rubber plugs, then charged with dry air.
- Piston options include externally accessible body for easy piston change out and/or TXV installation.
- Liquid line refrigerant connections are 3/8″ ODF.
- Suction line refrigerant connections are 7/8″ ODF.
- Microban® antimicrobial additive to inhibit the growth of mold and mildew in the drain pan.
- UV resistant drain pans are molded of high temperature (450° F) engineered polymer.
- Cased coil cabinets are fully lined with 5/8″ foil faced insulation.
- Non-captive refrigerant lines with long stubs make for easy installation.
- Copper distributor tube assembly provides brass to brass threads for trouble-free service of TXV.
- Corrosion resistant coil header plates.
Nomenclature
- Depth is fixed, 10″ is the only selectable option.
- Cabinet opening width is not a selectable option; see dimensions.
- Piston will always be sized to match the nominal BTU rating of the coil.
R-410A Pistons | ||
MBTUH | Size | |
12 | = | 41 |
18 | = | 49 |
24 | = | 53 |
30 | = | 59 |
36 | = | 67 |
42 | = | 73 |
48 | = | 76 |
60 | = | 93 |
HH Series – Specifications
- A = Height
- B = Width
- C = Depth (excluding flange)
- Supply Opening: (A – 1.50″) x (B – 4 3/8″)
- Return Opening: (A – 1.50″) x (B – 4 3/8″)
Weight / Pallet Qty
Slab Num | Weight (lbs) | Pallet Quantity |
H57 | 36 | 6 |
H58 | 41 | 4 |
H59 | 44 | 4 |
H60 | 50 | 4 |
H61 | 57 | 3 |
H62 | 61 | 3 |
H66 | 75 | 3 |
Dimensions
Slab Number | Nominal Tonnage |
Overall | Supply/Return Opening | |||
Height [A] | Width [B] | Depth [C] | Height | Width | ||
H57 | 1.5 – 3 | 22 3/4″ | 23″ | 10″ | 21 1/4″ | 18 5/8″ |
H58 | 2 – 4 | 22 3/4″ | 27″ | 10″ | 21 1/4″ | 22 5/8″ |
H59 | 2.5 – 4 | 22 3/4″ | 31″ | 10″ | 21 1/4″ | 26 5/8″ |
H60 | 3 – 5 | 22 3/4″ | 35″ | 10″ | 21 1/4″ | 30 5/8″ |
H61 | 3.5 – 5 | 22 3/4″ | 41″ | 10″ | 21 1/4″ | 36 5/8″ |
H62, H66 | 3 – 5 | 22 3/4″ | 47″ | 10″ | 21 1/4″ | 42 5/8″ |
Airflow Data
Slab Number | Wet Coil Air Pressure Drop (Inches W.C.) by CFM | |||||||
600 | 800 | 1000 | 1200 | 1400 | 1600 | 2000 | 2400 | |
H57 | .17 | .19 | .22 | .25 | – | – | – | – |
H58 | – | .18 | .20 | .22 | .24 | .26 | – | – |
H59 | .05 | .08 | .11 | .15 | .19 | .23 | – | – |
H60 | – | – | – | .17 | .18 | .23 | .27 | – |
H61 | – | – | – | – | .19 | .21 | .25 | – |
H62 | – | – | – | .15 | .17 | .19 | .23 | .27 |
H66 | – | – | .08 | .11 | .14 | .17 | .23 | .31 |
- 2175 West Park Place Boulevard