PEPPERL FUCHS KFD2-BR-1.PA.1500 Basic Segment Coupler Installation Guide

Home » Pepperl Fuchs » PEPPERL FUCHS KFD2-BR-1.PA.1500 Basic Segment Coupler Installation Guide

PEPPERL FUCHS logoBasic Segment Coupler
KFD2-BR-1.PA.1500

KFD2-BR-1.PA.1500 Basic Segment Coupler

PEPPERL FUCHS KFD2 BR 1 PA 1500 Basic Segment Coupler

  • Output: 24 … 26 V/400 mA
  • Couples PROFIBUS PA devices transparently to PROFIBUS DP
  • High-power trunk for high device count and long cable lengths
  • Installation in Zone 2/Class I, Div. 2
  • Up to 1.5 MBit auto-adapting
  • PROFIBUS DP terminator selectable
  • Power Rail support

Function

The FieldConnex® basic Segment Coupler is an all-in-one gateway and fieldbus power supply for connecting PROFIBUS PA to PROFIBUS DP transparently. The power output suits long cable lengths and high device counts. Device  couplers provide explosion protection for live work at the spur where needed.
Communication is transparent between DP and PA. The gateway of the Segment Coupler makes each PA device appear as if it was connected to DP: This relates to addressing, cyclic/acyclic data exchange, and the transfer rate. Segment  design is clear and easy to understand without subnetworks. The gateway itself is configuration-free. All in all, these features significantly reduce engineering work.
Availability and a long service life are achieved through a passive impedance filter and a design optimized for low heat dissipation. The fieldbus diagnostic handheld (FDH‑1) connects directly to test plug sockets located on the plug-in terminal.

Connection

PEPPERL FUCHS KFD2 BR 1 PA 1500 Basic Segment Coupler - Connection

Technical Data

General specifications
Design / Mounting Cabinet installation
Supply
Connection Power Rail or terminals 11 (L+), 12 (L-)
Rated voltage 20 … 30 V DC
Ripple ≤ 10  %
Rated current 640 mA … 365 mA
Power dissipation max 2.5 W
Fieldbus connection
PROFIBUS PA
Connection 3+, 6+, 2-, 5-, 1 shield, 4 shield
Rated voltage 24 … 26 V
Rated current max. 400 mA
Terminating impedance 100 Ω , integrated
PROFIBUS DP PROFIBUS with RS-485 transmission technology
Connection terminals 7 RxD/TxD-P, 8 RxD/TxD-N, 9 shield, 10 FE
Baud rate 1.5 MBit/s max.
Indicators/operating means
Switch PROFIBUS DP terminator
LED PWR green: Power on
LED DP/ERR red 2 Hz flashing: DP error red on: Hardware error red off: DP communication detected
LED PA red 2 Hz flashing: No PA communication or overload Off: PA communication OK
Galvanic isolation
PROFIBUS DP/PROFIBUS PA functional insulation acc. to IEC 62103, rated insulation voltage 50 V AC /70 V DC
PROFIBUS DP/Supply basic insulation according to IEC/EN 61010, rated insulation voltage 253 V AC /357 VDC
PROFIBUS PA/Supply basic insulation according to IEC/EN 61010, rated insulation voltage 253 V AC /357 VDC
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013
Standard conformity
Electromagnetic compatibility NAMUR NE 21
Degree of protection IEC/EN 60529
Fieldbus standard EN 50170/2
Climatic conditions DIN IEC 721
Shock resistance EN 60068-2-27
Vibration resistance EN 60068-2-6
Ambient conditions
Ambient temperature -40 … 60 °C (-40 … 140 °F)
Storage temperature -40 … 85 °C (-40 … 185 °F)
Relative humidity < 95 % non-condensing
Shock resistance 15 g 11 ms
Vibration resistance 1 g 10 … 150 Hz
Pollution degree max. 2, according to IEC 60664
Corrosion resistance acc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Connection type Terminals
Core cross section up to 2.5 mm
Housing material Polycarbonate
Degree of protection IP20
Mass 180 g
Mounting DIN rail mounting
Data for application in connection with hazardous areas
Certificate TÜV 16 ATEX 7831 X
Marking 1 II 3G Ex ec IIC T4 Gc
Directive conformity
Directive 2014/34/EU EN IEC 60079-0:2018+AC:2020 ,  EN 60079-7:2015+A1:2018
International approvals
CSA approval CSA 16.70064204
Approved for Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, Ex nA IIC T4 Gc
IECEx approval IECEx TUR 16.0006X
Approved for Ex ecc IIC T4 Gc
General information
Supplementary information Statement of Conformity, Declaration of Conformity, Attestation of Conformity and
instructions have to be observed where applicable. For information see www.pepperlfuchs.com.

Assembly

PEPPERL FUCHS KFD2 BR 1 PA 1500 Basic Segment Coupler - Assembly

Accessories

PEPPERL FUCHS KFD2 BR 1 PA 1500 Basic Segment Coupler - icon1 UPR-03 Universal Power Rail with end caps and cover, 3 conductors, length: 2 m
PEPPERL FUCHS KFD2 BR 1 PA 1500 Basic Segment Coupler - icon2 KFD2-EB2 Power Feed Module
PEPPERL FUCHS KFD2 BR 1 PA 1500 Basic Segment Coupler - icon3 KFD2-EB2.R4A.B Power feed module, redundant supply

Basic Segment Coupler

Additional Information

Dimensions and Assembly

PEPPERL FUCHS KFD2 BR 1 PA 1500 Basic Segment Coupler -Dimensions

 

Description:

  1. Extendable lugs
  2. PROFIBUS DP connection
  3. Switch: Terminator for PROFIBUS DP
  4. LED PA: Status of PROFIBUS PA
  5. LED DP: Status of PROFIBUS DP and hardware
  6. LED PWR: Status of power supply
  7. Removable terminal with test plug sockets
  8. PROFIBUS PA trunk connections

PEPPERL FUCHS logoRefer to “General Notes Relating to Pepperl+Fuchs Product Information”.
Pepperl+Fuchs Group
www.pepperl-fuchs.com
USA: +1 330 486 0002
[email protected]
Germany: +49 621 776 2222
[email protected]
Singapore: +65 6779 9091
[email protected]
Release date: 2023-06-21
Date of issue: 2023-06-21
Filename: 277830_eng.pdfPEPPERL FUCHS KFD2 BR 1 PA 1500 Basic Segment Coupler - icon