1500W Pure Sine Wave
SD1500 series
Contents
Features:
- Parallel redundancy design for power expansion
- Multiple industrial applications that create 1Ф3W / 3Ф4W power systems
- Automatic master mechanism to eliminate single point failure and optimize reliability
- Built-in ATS and AC circuit breaker
- Optional STS module, transfer time less 4ms.
- RS-232 communication
- Input & output fully isolation
- Output voltage / power saving mode selectable by DIP switch or remote control (CR-10)
- Input Protection: Reverse Polarity (Fuse) / Under Voltage / Over Voltage
- Output Protection: Short Circuit / Overload / Over Temperature / Over Voltage
LED Status:
Green LED | LED Signal | Status |
Solid | ![]() |
Power OK |
Slow Blink | ![]() |
Power Saving |
Intermittent Blink | ![]() |
Bypass |
Orange LED | LED Signal | Status |
Fast Blink | ![]() |
OVP |
Slow Blink | ![]() |
UVP |
Red LED | LED Signal | Status |
Intermittent Blink | ![]() |
OTP |
Fast Blink | ![]() |
OVP- Shut-down |
Slow Blink | ![]() |
UVP- Shut-down |
Solid | ![]() |
OLP |
Intermittent Blink | ![]() |
Fan Failure |
Intermittent Blink | ![]() |
Component Failure |
Output Socket:
Input Socket:
De-rating Curve:
Transfer Time :
Transfer-Time Table | ||
Model Transfer Switch | ATS | STS |
Haphazard | Inverter to utility AC : 8~10ms.; Utility AC to inverter :16 ~ 50ms. |
Frequency is synchronized : <4ms Frequency is not synchronized : Inverter to utility AC : <4ms.; Utility AC to inverter :16 — 50ms. |
Normal (Default) | Inverter to utility AC : 8~10ms.; Utility AC to inverter :16 ~ 25ms. |
<4ms |
Exacting | Inverter to utility AC : 8~10ms.; Utility AC to inverter :16 ~ 50ms. |
Inverter to utility AC : <4ms.; Utility AC to inverter :16 — 50ms. |
Online | Inverter to utility AC : 8~10ms.; Utility AC to inverter :16 ~25ms. |
<4ms |
Mechanical Drawings:
Unit : mm [inch]
REV. A9
22/09/20
3