INSTALLATION INSTRUCTIONS FOR EN54-23 W CLASS WALL MOUNTED LOOP POWERED ADDRESSABLE SOUNDER STROBES.

MODELS

WRA-xC-I05 = Sounder Strobe Isolation Red Flash
WWA-xC-I05 = Sounder Strobe Isolation White Flash

Adjustable performance
Wall Mounted Sounder Strobe

x = Denotes body colour (P – Pure White, R – Red)

Honeywell WRA-xC-I05 Sounder Strobe Isolation Red Flash

GENERAL

The range is used in analogue addressable fire alarm systems.
These devices must only be connected to control panels that use a compatible proprietary analogue addressable communication protocol.
These devices receive their power from the loop, and can be controlled via the communication protocol(s).
Note: if the control equipment is not capable of taking over 99 module addresses, a fault condition will be generated for every address over 99.
For isolator specification refer to document S00-7400 available on request.

V (isolation) 15 to 29VDC
(24VDC typical)
I (max) @24V) High Output
Standard Output
Legacy Output
25.2mA
21.2mA
16.2mA
P (max) High Output
Standard Output
Legacy Output
605mW
509mW
389mW
Honeywell WRA-xC-I05 - Sound output EN54-3 (sound output)
(High Volume Tone 8 @24V)

96dB(A) ± 3dB

Honeywell WRA-xC-I05 - Terminal size (terminal size) 2.5mm²
maximum
Honeywell WRA-xC-I05 - Flash rate (flash rate)

0.5 &1Hz

Honeywell WRA-xC-I05 - Standby mode (standby mode)

130uA

°C (operating temperature)

-10°C to +55°C

Honeywell WRA-xC-I05 - Humidity% (humidity)

up to 96% (± 3%) non condensing

IP rating

IP 21C

Disposal Icon 19

This symbol on our product shows a crossed-out “wheelie-bin” as required by law regarding the Waste of Electrical and Electronic Equipment (WEEE) disposal. This indicates your responsibility to contribute in saving the environment by proper disposal of this Waste i.e. Do not dispose of this product with your other wastes.
To know the right disposal mechanism please check the applicable law.

KAC ALARM COMPANY LIMITED, Honeywell House, Skimped Hill Lane, Bracknell, Berks, RG12 1EB. T. 02034091779 E. [email protected] W. www.kac.co.uk

Honeywell WRA-xC-I05 - INSTALLATION 1 INSTALLATION / PRODUCT ORIENTATION

Affix B501AP to a suitably flat wall. Terminate the cable to the appropriate terminals. For surface mount wiring the cable can enter the B501AP via the break outs provided. Select the appropriate Light Coverage, Tone and Volume settings via the DIP switch.

Make sure the product is fitted in the correct orientation!

Honeywell WRA-xC-I05 - INSTALLATION 2

Scan the barcode below to see the correct fitting to the wall:

Honeywell WRA-xC-I05 - QR Code 1

Honeywell WRA-xC-I05 - CONTINUITY SPRING 1 CONTINUITY SPRING

The B501AP incorporates a continuity spring between terminals 2 and 4. This allows the continuity of the field wiring to be checked without the need for the device to be present. Inserting the device will disengage the spring.
Removing the device will close the loop.

Honeywell WRA-xC-I05 - CONTINUITY SPRING 2

Honeywell WRA-xC-I05 - TERMINAL CONNECTIONS 1 TERMINAL CONNECTIONS

Honeywell WRA-xC-I05 - TERMINAL CONNECTIONS 2

Honeywell WRA-xC-I05 - ANTI TAMPER RELEASE 1 ANTI TAMPER RELEASE

Honeywell WRA-xC-I05 - ANTI TAMPER RELEASE 2

Honeywell WRA-xC-I05 - ANTI TAMPER RELEASE 3

IMPORTANT: Follow the instruction strictly:
1) Insert a flat screwdriver
2) Lever the screwdriver down and twist the device anticlockwise.
3) Remove the screwdriver to unlock the device.

For a full video on how to release the anti-tamper feature please scan the QR code:

Honeywell WRA-xC-I05 - QR Code 2

Table 1 (Tone selection)

Honeywell WRA-xC-I05 - Table 1

Address settings

Honeywell WRA-xC-I05 - Address settings

S1 S2
Address 108 = 10   8

  1. Switch 1
  2. Switch 2

To set one of the 159 available addresses for the device use the two rotary switches located either side of the dip switch unit. The ‘tens’ digits goes from 0 to 15 and the ‘units’ from 0 to 9. *100 – 159 Only available with advanced protocol.

Dimensions

Honeywell WRA-xC-I05 - Dimensions 1

Honeywell WRA-xC-I05 - Dimensions 2

Volume, coverage and frequency settings

Honeywell WRA-xC-I05 - Volume, coverage and frequency settings

  1. (Refer to table 1 )
  2. (Refer to table 2 )

DIP setting 0=Off/1=On.

Table 2

ON OFF

SW6

Honeywell WRA-xC-I05 - Volume LOW VOLUME HIGH VOLUME

SW7

Honeywell WRA-xC-I05 - coverage 0.5Hz
Red
(W-2.4-10.5/W-3.6-10.5)
White
(W-2.4-9/W-3.8-9)
0.5Hz
Red
(W-2.4-11.5/W-4.2-11.5)
White
(W-2.4-11.5/W-4-11.5)

SW8

f

1Hz (O-2.4-3) 0.5Hz (EN54-23 W Class)
Coverage data

EN 54-23

Led V X (Max) Y (Max) V (m ³)
W-4.2-11.5
W-2.4-11.5
RED 15-29V 4.2m
2.4m
11.5m
11.5m
555
317
W-3.6-10.5
W-2.4-10.5
RED 15-29V 3.6m
2.4m
10.5m
10.5m
397
265
O – 2.4 – 3 RED 15-29V 2.4 3m 21.6
W- 4 -11.5
W- 2.4-11.5
WHITE 15-29V 4m
2.4m
11.5m
11.5m
529
317
W-3.8-9
W-2.4-9
WHITE 15-29V 3.8m
2.4m
9m
9m
308
194
O – 2.4 – 3 WHITE 15-29V 2.4 3m 21.6

Honeywell WRA-xC-I05 - Coverage data

For the ‘O’ class detailed coverage data, in accordance with EN54-23, please request the following doc.: S00-7006

CE Icon              UKCA Icon
2831   23           0832  23
Morley IAS by Honeywell,
Pittway Tecnologica Srl, Via Caboto 19/3, 34147
Trieste, ItalyDOP050
EN 54-3:2001 +A1: 2002 + A2:2006
Fire detection and fire alarm systems – SoundersEN54-23:2010
Fire detection and fire alarm systems – Visual Alarm DevicesEN 54-17:2005
Fire detection and fire alarm systems – Short-circuit isolators.W*A-*C-I05

For LPCB: approved to EN 54-3: 2014 + A1: 2019.
Sounder Output data, in accordance with EN54-3, is available on Document Ref: S00-7005

I56-5003-000